Send Message
Home ProductsUPS Lead Acid Battery

UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery

Certification
China SUZHOU FOBERRIA NEW ENERGY TECHNOLOGY CO.,LTD. certification
China SUZHOU FOBERRIA NEW ENERGY TECHNOLOGY CO.,LTD. certification
Customer Reviews
This is a fantastic sourcing battery supplier, considerate service and good quality product.

—— Olga

Good Products ,Good Service,Good Battery Supplier, for producing different types of battery,like ups battery,solar battery.

—— Ravil

A reliable battery supplier, cooperation is very happy!

—— Annie

We have very strict requirements for the battery we purchase, Foberria battery meets the requirements, not only the product quality is good, but also the service.

—— Omar

I'm Online Chat Now

UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery

UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery
UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery

Large Image :  UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery

Product Details:
Place of Origin: CHINA
Brand Name: FOBERRIA
Certification: CE / ISO9001
Model Number: FBR12-4
Payment & Shipping Terms:
Minimum Order Quantity: 50pcs
Price: Negotiable
Packaging Details: Cartons with pallet
Delivery Time: 25-30days
Payment Terms: L/C, T/T, Western Union
Supply Ability: 60,000 per month

UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery

Description
Name: UPS Battery Model: FBR12-4
Voltage: 12V Capacity: 4ah,7ah
Weight: 1.35kg±5% Terminal: F1
Color: Black/Gray Usage: UPS,Solar System
Feature: Low Self Discharge Application: UPS,Solar System
Batttery Type: Deep Cycle Rechargeable Battery Sealed Type: Sealed
Long Life: 10 Years
High Light:

12v sealed Lead acid battery

,

12v UPS Stroage Solar battery

,

Sealed UPS Stroage battery

UPS battery 12v series 4ah/7ah small sealed Lead acid agm power supply for Stroage Solar battery

 

> Specification
Battery Model No.   FBR12-7 FBR12-4
Nominal Voltage   12V 12V
Capacity 20HR(10.8V) 7Ah 4Ah
(25ºC) 10HR(10.5V) 6.5Ah 3.7Ah
  1HR(9.6V) 4.5Ah 2.6Ah
Dimension Length 150±2mm 90±2mm
Width 65±2mm 70±2mm
Height 94±2mm 100±2mm
Total height 100±2mm 107±2mm
Approx. Weight 2.1kg±5% 1.35kg±5%
Terminal type F1/F2 F1/F2
Internal resistance(Fully charged,25ºC) Approx 30 Approx 55
Capacity affected by 40ºC 102% 102%
Temperature(20HR) 25ºC 100% 100%
0ºC 85% 85%
-15ºC 65% 65%
Self-discharge(25ºC) 3month Remaining Capacity:91% Remaining Capacity:91%
6month Remaining Capacity:82% Remaining Capacity:82%
12month Remaining Capacity:65% Remaining Capacity:65%
Nominal operating temperature 25ºC±3ºC(77ºF±5ºF) 25ºC±3ºC(77ºF±5ºF)
Operating Discharge -15ºC-50ºC(5ºF-122ºF) -15ºC-50ºC(5ºF-122ºF)
temperature range Charge -10ºC-50ºC(14ºF-122ºF) -10ºC-50ºC(14ºF-122ºF)
  Storage -20ºC-50ºC(-4ºF-122ºF) -20ºC-50ºC(-4ºF-122ºF)
Float charging voltage
(25ºC)
13.5 to 13.8V
Temperature compensation:-18mV/ºC
13.5 to 13.8V
Temperature compensation:-18mV/ºC
Cyclic charging voltage
(25ºC)
14.5 to 15V
Temperature compensation:-30mV/ºC
14.5 to 15V
Temperature compensation:-30mV/ºC
Max charging current 2.1A 1.2A
Max discharging current 105A(5sec.) 60A(5sec.)
Designed floating life(20ºC) 5years 5years
 
 
>Structure and composition
 
Component Positive plate Negative plate Container Cover Separator Electrolyte Safety valve Terminal
Raw material Lead dioxide Lead ABS ABS AGM Sulfuric acid Rubber Copper
 
UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery 0
>Constant Current Discharge Characteristics(A,25ºC)
 
F.V/Time 10min 15min 30min 60min 2h 3h 4h 5h 8h 10h 20h
9.6V 262 202 121 74.2 43.8 31.2 25.2 21.5 14.8 12.2 6.47
9.9V 254 197 118 73 43.6 31 25.1 21.4 14.7 12.2 6.46
10.2V 243 190 115 71.2 43.2 30.8 24.9 21.3 14.6 12.2 6.44
10.5V 233 183 112 69.7 42.6 30.6 24.7 21.1 14.5 12.1 6.4
10.8V 220 173 108 67.6 41.5 29.7 24 20.5 14.1 12 6.36

 

 

>Constant Power Discharge Characteristics(Watt,25ºC)

 

F.V/Time 10min 15min 30min 60min 2h 3h 4h 5h 8h 10h 20h
9.60V 2825 2214 1353 845 508 367 297 255 176 146 77.7
9.90V 2741 2160 1326 833 505 365 295 253 175 146 77.5
10.2V 2628 2081 1285 812 500 362 293 251 174 145 77.3
10.5V 2514 2010 1254 795 493 360 291 250 172 144 76.9
10.8V 2373 1904 1208 770 480 349 282 242 167 143 76.3
 
 
>Discharge diagram
 
UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery 1
UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery 2

 

> Product Primary competitive advantges

1. 100% Pre-delivery inspection to ensure stable quality and reliable performance.
2. Pb-Ca grid alloy battery plate, low water loss, and stable quality low self-discharge rate.
3. Low internal resistance, good high rate discharge performance.
4. Excellence high-and-low temperature performance, working temperature ranging from -25°C to 50°C.
5. Design float service life: 5-7 years.

 
>Production process
UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery 3
 
>Workshop scene
UPS Battery 12v Series 4ah 7ah Small Sealed Lead Acid Agm Power Supply UPS Stroage Solar Battery 4
 
>Daily maintenance and operation

 

Discharge

 

1.Do not let the terminal voltage drop below the terminal voltage;

 

2.Do not leave the battery in a discharged condition. Recharge it immediately. Also when the battery has been over discharged by mistake,

 

recharge it immediately;

 

3.The maximum permissible discharge current 6C amps discharge for 5 seconds or less, do not exceed this value,

 

otherwise it may damage the battery.

 

Charge

 

1.Float charge


The floating charge voltage should remain constant;

 

The effects of too high or too low a floating charge voltage is as follows:


Too high for extended period (overcharge): it may shorten battery life


Too low for extended period (undercharge):

 

it may not meet load or cause variances in battery voltage that will decrease the capacity of battery pack and shorten their life.

 

2.Recovery charge

 

When resuming charging, the initial current should be limited to 0.1C-0.3CA;

 

3.Temperature compensation


When the temperature deviates from 25℃, please modify the voltage as 3mv/cell fo every 1C deviation.

 

3.The equalizing charge


The equalizing charge voltage is 2.30 - 2.35V/cell.

 

4.Cautions during charge


(a)If the charge current exceeds 0.05CA at the final stage of charge, the storage batter may be permanently damaged in appearance and life.

 

Pay special.attention to charging voltage.


(b)The battery charger should be the one that can provide automatic constant voltage with drooping characteristics, if other types will be used,

 

please contact us before applied.

 

 

STORAGE

 

1.When you wish to store the battery, battery should be stored without charger and load at dry location with low temperature.

2.If batteries are stored for a long period, give a supplementary charge before use.

 

 

Contact Details
SUZHOU FOBERRIA NEW ENERGY TECHNOLOGY CO.,LTD.

Contact Person: Mr. Roger Ning

Tel: +86 139 6163 5976

Fax: 86-512-50176362

Send your inquiry directly to us (0 / 3000)